Our Products
High Voltage Distribution
Low Voltage Distribution
news & events
Happy Holy
09/04/2016
Happy Holi to all of you.

From Team
Asiatic
 
Happy Navratra
09/04/2016

We at Asiatic Electrical and Switchgear Pvt. Ltd. wishes to our customers from all over the world " HAPPY NAVRATRA".

May this festival brings lots of joy and happiness in your life.

 
Launching New Website
06/08/2015

Announcing launch of our new website in August 2015 with added information & new product categories. Sending inquires couldn't have been easier...... 

 
Approved in KAHRAMAA - QATAR
06/08/2015

It gives us great pleasure in informing our customers that we are now approved in  KAHRAMAA - Qatar for supply of LV Feeder Pillars..... 

 
 
 
contact us
ASIATIC ELECTRICAL & SWITCHGEAR PVT. LTD.

Registered Office:
A 58 Naraina Industrial Area, Phase-I, New Delhi - 110028, India.

Tel.: +91-11-25796330

Fax: +91-11-25799816, 45082346
E-mail: sales@asiatic-india.com
Website: www.asiatic-india.com
60/80/100AMP SP/SPN/TPN HOUSE SERVICE CUTOUT
click on above pictures to view enlarge view !
 
The cutouts are designed for 60/80/100A rating complying with BS 7657:1993 and ESI 12-10.


General Construction
The Cutout Housing is of DMC with a quality finish from modern moulding tools to ensure accuracy in the various 

parts for interchangeability. Mechanical and Di-electric strength. Brass inserts are provided wherever required for 

fixing one part to another. Terminal Blocks are of Brass duly Tin plated, fitted with two large pinching screws per 

conductor. The fuse carriers are designed for standard BS 88 / BS 1361 fuse links and standard copper contacts 

having uniform pressure to ensure effective contact with long service life. 

Following dimensions are standard:
Upto 60/80A 22.23 mm dia.-57 mm long II a
80/100A 30.16 mm dia.-57 mm long II b

Fuse Carriers: These are of split design, therefore it only necessitates to loosen the fuse clips when replacing a 

fuse link. Fuse link can be withdrawn from the open end of the carrier half. Carrier housing is common for both 60A 

& 100A fuse links. Upgrading of cutout can be done simply by replacing with larger fuse clips. 


Sealing: The fuse carrier and fuse base unit have provision for wire sealing. An additional wire sealing 

arrangement is provided for the neutral.
Phase Protection: A hinge type nylon shroud covers the incoming phase terminals thus reducing the possibility of 

accidental contact with live parts when wiring the outgoing terminal.

Interlocking Feature: Prior to removal of any component, the fuse carrier has to be withdrawn. This enables clear 

access to the neutral block and/or cable trough. This is an inbuilt safety feature.

Terminals
The design and construction of the cutouts ensures terminals to be retained without the use of any fixing screws. 

Adequate size serrated bores and pinching screws are provided for standard Copper or Aluminum and solid conductors 

of upto 35 sq. mm. on phase and neutral. The neutral/earth block of the cutout also has bores for two earth 

conductors and connection for a time switch wire. Cabling: The cable trough is designed for termination, suitable 

for PVC cables. In addition a small knockout is provided for an externally connected earth wire when using a PILCA 

cable.

Type Tests

The cutout has been tested for the following Type Tests as per BS 7657:
* Test for temperature rise at rated current.
* Mechanical endurance (including repeat of test for temperature
rise at rated current).
4Overload test (including repeat of test for temperature rise at rated
current, lightning impulse withstand voltage dry tests and power
frequency withstand voltage dry tests).
* Performance under short-circuit conditions.
* Flammability test.
* Impact test.
* Strength of sealing lugs.
* Degree of protection test (Ip4x).
* Terminal torque test.

Routine Test
* H.V. Test at 3.75 kV (rams) for one minute.
* Insulation resistance test.
* Mechanical insertion & withdrawal test.
 
Technical Specification
  Type/Data
60/80A SP
100A SP
60/80A SPN
100A SPN
100A TPN
  Rated Operating Voltage Ue
415V
415V
415V
415V
415V
  Rated Operational Current in
60/80A
100A
60/80A
100A
100A
  Rated Insulation Voltage Ui
660V
660V
660V
660V
660V
  Rated Short Time Current Lcw
12 kA Peak 0.02 Sec
18 kA Peak 0.02 Sec
12 kA Peak 0.02 Sec
18 kA Peak 0.02 Sec
18 kA Peak 0.02 Sec
  Impulse Voltage U imp
6 kV with 1.2/50µs waveform
6 kV with 1.2/50µs waveform
6 kV with 1.2/50µs waveform
6 kV with 1.2/50µs waveform
6 kV with 1.2/50µs 6 kV with 1.2/50µs waveform
  Cable Size upto
35 sq. mm
35 sq. mm
35 sq. mm
35 sq. mm
35 sq. mm
  Fuse Link Cartridge
As Per BS 1361 Type II a*
As Per BS 1361 Type II b
As Per BS 1361 Type II a*
As Per BS 1361 Type II b
As Per BS 1361 Type II b
  Sealing Arrangement Provided
Yes
Yes
Yes
Yes
Yes